VISTA-15P
|
Product FAQ
|
| Programming Relay to Reset 4-Wire Smoke Detectors (ID:12802466) |
|
The following will explain how to setup a 4204 relay module for 4-wire smoke reset.
Watch out for: o You must use a zone that is not intended for 2-wire smoke detectors. o The panel will not reset unless it sees a maintained short on a fire zone. o Make sure the 4204 is the correct device address and programmed properly. Document links: Detailed Notes For Vista-32/40/50/100/128/250 Detailed Notes For Vista-15P or 20P Detailed Notes For Vista-15P(rev2+) Vista-20P(rev2+) Vista-15Ps Vista-20Ps |